EAN: 8592765133946
Air Switch Disconnectors Ex9ASD are used as main switch in various industrial applications, such as high current rated installations that may require high prospective short circuit current on power distribution systems among others. Testing according IEC / EN 60947-3 standard ensures function and reliability on a wide variety of applications including isolation.
Paremeter | Value |
---|---|
Type of electrical connection of main circuit | Other |
Version as maintenance-/service switch | NO |
Suitable for front mounting 4-hole | NO |
Suitable for distribution board installation | YES |
Colour control element | Green |
Rated short-time withstand current lcw | 85 |
Number of auxiliary contacts as change-over contact | 0 |
Version as safety switch | NO |
Version as reversing switch | NO |
Version as emergency stop installation | NO |
Number of poles | 3 |
Suitable for intermediate mounting | NO |
Type of control element | Push button |
Degree of protection (IP), front side | IP40 |
Suitable for ground mounting | YES |
Rated operating voltage | 690 |
Rated permanent current Iu | 4000 |
Motor drive integrated | NO |
Voltage release optional | YES |
Suitable for front mounting center | NO |
Device construction | Built-in device slide-in technique (withdrawable) |
Version as main switch | YES |
Motor drive optional | YES |
Document Type | Document Name | Size | Format |
---|---|---|---|
Ex9A Fast installation guide | 21.5mb | ||
EU Declaration of conformity Ex9ASD40 | 0.2mb | ||
EU Declaration of conformity Ex9ASD25 | 0.2mb | ||
EU Declaration of conformity Ex9ASD16 | 0.2mb | ||
Arkusz danych Ex9ASD | 22.4mb |